Article

Simulation of Fluid-Thermal Field in Oil-Immersed
Transformer Winding Based on Dimensionless
Least-Squares and Upwind Finite Element Method
Gang Liu 1,*, Zhi Zheng 1, Dongwei Yuan 1, Lin Li 2 and Weige Wu 3
Hebei Provincial Key Laboratory of Power Transmission Equipment Security Defense, North China Electric
Power University, Baoding 071003, China; zhengzhi0013@163.com (Z.Z.); ydw2046@163.com (D.Y.)
2 State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources, North China
Electric Power University, Changping District, Beijing 102206, China; lilin@ncepu.edu.cn
3 Baoding Tianwei Baobian Electric Co., Ltd, Baoding 071056, China; weigewu@163.com
* Correspondence: liugang@ncepu.edu.cn; Tel.: +86-312-752-2854
1

Received: 22 August 2018; Accepted: 4 September 2018; Published: 6 September 2018

Abstract: In order to study the coupling fluid and thermal problems of the local winding in
oil-immersed power transformers, the least-squares finite element method (LSFEM) and upwind
finite element method (UFEM) are adopted, respectively, to calculate the fluid and thermal field in
the oil duct. When solving the coupling problem by sequential iterations, the effect of temperature
on the material property and the loss density of the windings should be taken into account. In order
to improve the computation efficiency for the coupling fields, an algorithm, which adopts two
techniques, the dimensionless LSFEM and the combination of Jacobi preconditioned conjugate
gradient method (JPCGM) and the two-side equilibration method (TSEM), is proposed in this
paper. To validate the efficiency of the proposed algorithm, a local winding model of a transformer
is built and the fluid field is computed by the conventional LSFEM, dimensionless LSFEM, and the
Fluent software. While the fluid and thermal computation results of the local winding model of a
transformer obtained by the two LSFEMs are basically consistent with those of the Fluent software,
the stiffness matrix, which is formed by the dimensionless scheme of LSFEM and preconditioned
by the JPCGM and TSEM, has a smaller condition number and a faster convergence rate of the
equations. Thus, it demonstrates a broader applicability.
Keywords: oil-immersed power transformer; least-square finite element method; upwind finite
element method; fluid-thermal coupling; dimensionless analysis

1. Introduction
As the core equipment of power systems, power transformers are usually used for power
transfer and voltage alternating, and its reliable operation is the premise to guarantee the quality of
the power supply. Therefore, manufacturers and researchers are continuously committed to
improving their performance and prolonging their life expectancy [1]. The service life of a
transformer is dictated mainly by the aging of the paper insulation, which is affected in turn by the
maximum temperatures in the various components during its operation. During the operation of the
transformer, a small portion of the electrical energy gets lost in the form of heat during the
transmission. For the forced oil circulation, the cold oil is pumped into the transformer through the
inlet by the oil pump and contacts the heat generating components such as the iron core and
windings through the oil duct; it absorbs the heat and then flows out of the tank through the outlet.
Energies 2018, 11, 2357; doi:10.3390/en11092357

www.mdpi.com/journal/energies

Energies 2018, 11, 2357

2 of 17

For the nature oil circulation, the hot oil, which contacts the inner wall of the tank, flows upward
after absorbing the heat and then transfers it to the tank; the tank transfers heat to air in the end.
After cooling, the oil flows downward. Due to the convective circulation of oil, a closed loop is
formed. In short, acting as the medium of heat transfer, the oil is the most important part of the
cooling system in transformers [2,3]. If the cooling system is not designed appropriately, the
overheating phenomenon of the components will occur [4–6]. As mentioned in Reference [7], in the
hotspot, the depolymerization process of cellulose insulation gradually emerges, which will degrade
the mechanical properties of cellulose paper, such as tensile strength and elasticity, and makes the
paper brittle and incapable of enduring electrical forces and vibrations. This irreversible
deterioration strongly affects the transformers service life. To ensure the normal operation of the
transformer, the temperature must be kept below a critical level by effectively dissipating the
generated heat [8,9]. The use of oil as insulation material has proven to be very efficient in
dissipating the heat and it displays unique dielectric properties as well, which makes the oil
immersed cooling type of power transformer widely applied in high voltage power transmission
systems. Since the flow distribution in the cooling channel directly affects the operation temperature,
the adoption of proper cooling systems is critical to the thermal management of transformers [10]. To
get a better understanding of the thermal behavior and to optimize the thermal performance of
oil-immersed transformers, the characteristics of oil flow velocity and temperature distribution has
been analyzed and discussed by numerical simulations techniques [11–27].
Torriano et al., [10] numerically studied the impacts of the operational parameters, such as the
mass flow rate and boundary conditions on the flow and temperature distributions of the windings.
As can be concluded, the higher the flow rate, the better cooling effect of the windings can be
achieved. With a more uniform temperature distribution in the windings, the hotspot temperature
decreases. Kranenborg et al., [12] conducted computational fluid dynamics (CFD) simulations on a
winding consisting of six partitions. They noted that the formation of hot streaks in the fluid and
recognized their great influence on the downstream temperature distribution. In the literature in
Reference [10], Skillen et al., [13] conducted a more detailed study on predicting the
mixed-convection flow of coolant in a low-voltage transformer winding. They explored the
generation mechanism of hot streaks and also found that there is a strong coupling among the flows
in different passes. The experimental devices of the local winding, the transformer slicing model,
and the entire structure of the transformer was established in the literature in Reference [20–23],
respectively. The thermal profile of a transformer was experimentally investigated from different
levels of complexity. Godina et al., [24] made a comprehensive review by analyzing and discussing
the existing studies on the effect of loads and other key factors on oil-transformer ageing. They
analyzed each relevant factor in detail and concluded that a monitoring system is essential to ensure
the reliable operation of a transformer. Ramos et al., [25] has developed a mathematical differential
model to represent the ventilation and the thermal performance of underground transformer
substations, and numerically solved it. By the simulations of the model, whose validity has been
verified by the temperature rise test, two important parameters related to the ventilation
performance of the substation were obtained. Recently, some researchers have combined the
response surface optimization method with the numerical calculation method to optimize the design
of the transformer cooling system [7,27]. Zhang et al., [27] constructed a 3-D computational fluid
dynamic model for a transformer to generate the training data for response surface method (RSM).
They employed two types of RSMs to evaluate their performance of designed cooling systems. A
comparison of the solution and the results obtained by the direct optimization method was
conducted to verify the effectiveness of the RSM in the design of an oil-immersed transformer
cooling system. Raeisian et al., [7] developed a numerical scheme to examine the effective
parameters on the thermal management of distribution transformers. The input variables in the
optimization procedure were considered to be the most effective ones. The results indicated that by
using the proposed optimum transformer configuration, a reduction of about 16 °C of hotspot
temperature is produced, as compared to the actual transformer. Moreover, a detailed literature
review of the study investigating the effects of cooling system design on the overall performance of
the transformers was presented in Reference [7]. Literature reviews show that an accurate and

Energies 2018, 11, 2357

3 of 17

comprehensive understanding of the thermal behavior inside the transformer is the key to optimize
the cooling system. As an electromagnetic-fluid-thermal field coupling problem, the calculation of
the temperature rise inside the transformer is rather complex. Therefore, it is necessary to find a
highly efficient and stable numerical method for multi-physics coupling problems [28–30].
At present, the numerical methods for multi-physics field coupling problems of
electromagnetic, fluid, and the thermal field of power transformers mainly include the finite volume
method (FVM) [12,14–16], finite element method (FEM) [17–19,28], and finite difference method
(FDM). The FVM is one of the most popular methods in the field of CFD. For example, the CFD
simulation software Fluent is based on the FVM. Compared to FVM, the FEM is applied to the
thermal calculation of fluid-solid boundary, which is directly coupled. It ensures the continuity of
heat flux and makes it suitable for thermal field calculation for complex boundaries and multi-media
[31]. However, the application of FEM usually leads to numerical oscillation and thus the numerical
distortion may appear when solving the convection-diffusion problems [32,33]. In view of this, a
grid refinement method is then proposed at the cost of increasing the computation amount. Another
method is the UFEM, which can effectively remove numerical oscillation without increasing its
computational cost [34,35]. In order to give full play to the advantages of various algorithms, some
researchers tried to use FVM to calculate the fluid field; when it comes to the thermal field, the
calculation method, which is good at dealing with the fluid-solid coupling boundary, was adopted.
For example, in Reference [36], the FVM and FEM were used to calculate a transformer model of
ZZDFPZ-321100/530 (CHINA XD GROUP CO., LTD, Xi’an, China). In order to avoid numerical
oscillation, the upwind schemes of FVM and FEM were introduced. In Reference [37], a hybrid
algorithm combining FVM with FDM was proposed and compared with FVM or FDM. The results
show that the hybrid algorithm compensates for the problems of poor adaptability to irregular
meshes and limited computational accuracy.
It can be seen from the above literature that the FVM is widely applied in fluid field analysis
for its high calculation accuracy and good stability of numerical solution. However, the
computation process of FVM is rather cumbersome, and the computation amount of each nodes’
iteration is large. While the overlapping grids can be used to speed up convergence, the
computation speed is still slow. The FEM can solve the velocity components of all nodes in the
whole fluid region simultaneously, but the mass conservation equation and momentum equation
needs to be solved by the iterative method. Therefore, the computational efficiency is not
satisfactory. Besides, the stiffness matrix obtained by the FEM is not a symmetric positive definite,
which makes it more difficult to solve the equations. In addition, the indirect-coupling methods are
often adopted to cope with velocity-pressure coupling problems, which needs a great amount of
computation.
In order to calculate the fluid field efficiently, the least-square finite element method (LSFEM),
based on the concept of minimizing the 2-norm of residuals, is adopted in this paper [38–40]. A
sparse symmetric and positive definite stiffness matrix formed by the LSFEM and the iterative
method can be used to solve the equations accurately and efficiently. Meanwhile, the
velocity-pressure coupling problems can be solved by direct-coupling methods with the LSFEM to
further improve the computational efficiency. Four examples of Kovasznay flow, steady
two-dimension and three-dimension backward-facing step flow, and unsteady flow around a
circular cylinder are calculated by using LSFEM and Fluent software, respectively [41]. The results
show that the accuracy of LSFEM is higher than that of FVM, and the results of the fluid field
calculated by the LSFEM have a high numerical stability; therefore, the LSFEM does not need an
upwind scheme or grid refinement to avoid numerical oscillation.
Xie et al., [42] applied the LSFEM to obtain the velocity distribution of the local oil duct in a
transformer, and then applied the UFEM to get the temperature distribution. When calculating the
fluid field of the transformer, the conventional Navier-Stokes equation was applied, and the results
were basically consistent with that of Fluent software. However, the convergence rate is too slow, or
in some cases, it even does not convergent. Doctor Xie also put forward a classical lid-driven cavity
model based on the conventional governing equation by the LSFEM and analyzed its validity and
convergence [43]. The calculation results are basically consistent with those of Ghia and others, but

Energies 2018, 11, 2357

4 of 17

the convergence rate is not ideal. The reason lies in that the coefficients of the conventional
Navier-Stokes equations differ greatly in orders of magnitude because of the great differences
among physical parameters. Thus, the condition number of the corresponding stiffness matrix may
be very large. Were it not handled properly, the iteration numbers might increase sharpely and
could even cause a large numerical deviation. In order to solve the equations with large condition
numbers, some preconditioning must be applied on them to reduce the condition number, and then
those equations can be solved by iterative methods such as the conjugate gradient method (CGM)
[44]. However, the preconditioned stiffness matrix may still have a large condition number, which
means the goals of good accuracy and fast convergence rate cannot be guaranteed. In the light of
this, two techniques are adopted in this paper. First, the dimensionless scheme, in which the
coefficients of the equations only include Reynolds number and 1, is adopted, and it has much
smaller difference in orders of magnitude [45]. Second, on the basis of Jacobi preconditioned
method, the two-side equilibration method (TSEM) is used to optimize the preferred matrix of the
Jacobi preconditioned conjugate gradient method (JPCGM), and the condition number of the
coefficient matrix is further reduced by making the norms of the matrix’s row (column) equal [46].
This paper adopts the dimensionless LSFEM, combining the precondition method of JPCGM
and TSEM, and UFEM to solve the coupling fluid-thermal fields separately. To validate the
proposed method, a local winding model of a transformer is built, and the results of the
fluid-thermal fields of the model and the convergence rates are analyzed and compared.
2. Mathematical Foundation of LSFEM
2.1. Governing Equations
The density of transformer oil vary a little, hence it can be regarded as incompressible fluid. The
incompressible flow of the transformer oil can be described by the mass conservation equation and
momentum equation, which are uniformly called Navier-Stokes equations:
 U = 0

(1)

(U )U + p − 2U = f

(2)

where U is the oil velocity vector, ρ is the oil density, μ stands for the dynamic viscosity of
transformer oil, p represents the pressure of fluid, and f is the density vector of external force.
The thermal field satisfies the energy conservation equation, as described in Equation (3):

(

)

  CpUT −   T = ST

(3)

where Cp is the specific heat capacity, λ represents the heat conductivity, and ST stands for the heat
source. The nodes in the solid domain have no velocities, thus, Equation (3) will degenerate into the
heat conduction equation. In this paper, the UFEM scheme is used to obtain the temperature field
distribution. The detailed derivation process is described in the literature [34,35].
The calculation process of the fluid-thermal coupling problems is depicted in Figure 1. The
LSFEM is used to get the fluid field distribution, while the UFEM is used to calculate the
temperature field. Then, the linearization iteration is carried out by the indirect coupling method.
The maximum temperature difference between the two iterations is used as the convergence
criterion, denoted by ε, which is set to 1 × 10−4 in this paper.

Energies 2018, 11, 2357

5 of 17

Start

Set initial
temperature

Calculate physical
properties and loss
density of windings

Calculate flow
field velocity
with LSFEM

Modify temperature

Calculating the
temperature field with
the upwind finite
element

△T≥ε?

Yes

No

end

Figure 1. Process of fluid-thermal coupling calculation.

The Navier-Stokes equations of the incompressible fluid are the second-order partial
differential equations (PDEs), and the LSFEM cannot be applied directly. It is necessary to introduce
the vorticity to convert the second-order PDEs to the first-order PDEs so as to get the u-p-ω scheme
of the Navier-Stokes equations [38]. In this paper, two different schemes of LSFEM are presented.
One is a conventional scheme, and the other is the dimensionless scheme. For the sake of simplicity,
this paper only gives the derivation process in two-dimensional rectangular coordinates.
2.2. Conventional Scheme of LSFEM
The first-order PDEs of the two-dimensional fluid can be obtained after introducing the
vorticity [38]. The specific forms in two-dimensional rectangular coordinates are as follows:


u v
+
=0

x y

 u
u p

= fx
u +  v + + 
y x
y
 x

  u v +  v v + p −   = f
y
 x
y y
x

u v

+ − =0

y x


(4)

where u and v are the components of the fluid velocity in the direction of x and y axis, fx and fy stand
for the components of the external force density in the direction of the x and y axis, and ω represents
the component of the vorticity in the direction of z axis.
For the nonlinear convection term in the Navier-Stokes equations, the linear iteration method is
adopted. Thus, Equation (4) can be transformed into a compact matrix form:

Energies 2018, 11, 2357

6 of 17

A( g ) = A1

g
g
+ A2
+ A0 g = f
x
y

(5)

in which


 1
0 0 0 



0
1 0 
 A =   u0
 1  0
 u0 0 −  



−1 0 0 

 0

 0
1 0 0





v
0
0 
0
 A2 = 
0
 v0 1 0 




0 0 0 
 1


0 0 0 0




0 0 0 0

A0 =

0 0 0 0


 0 0 0 1 




0
u

 
 
f

 xg = v
f
=

f 
p

 y
 



w
0

(6)

where u0 and v0 represent the velocity values after previous iteration.
The residual function can be defined by Equation (5):
R = A( g ) − f

(7)

In order to get the minimum 2-norm value of the residual, we constructed the residual function:

I ( g ) = A( g ) − f

(8)

2

According to the variation method, the following equation can be obtained:

2 ( A g )

T

( A  h − f ) d = 0

(9)



where, Ω is the solution domain, and h is the first-order variation of g.
With the triangular or quadrilateral grids applied, the unknown variables in the element can be
obtained by interpolating:
nd

g =  N n ( un ,vn , pn ,ωn )

T

(10)

n= 1

where g is the pending vector, Nn stands for the interpolating function, un, vn, pn, and ωn are the
velocity, pressure and vorticity of the nth node in the element respectively.
Let h = N, and substituting Equation (10) into Equation (9) yields:

 ( AN


1

, AN 2 ,

, AN n )

T

( AN

1

, AN 2 ,

, AN n ) GdΩ =

where G is the degree of freedom (DOF) vector of the node.

 ( AN


1

, AN 2 ,

, AN n ) fdΩ
T

(11)

Energies 2018, 11, 2357

7 of 17

Equation (11) can be written in the form of a compact matrix equation:

K G = F

(12)

where K is the global stiffness matrix, and F is right-hand side function.
2.3. Dimensionless Scheme of LSFEM
The general Navier-Stokes equation is treated dimensionless by the dimensionless LSFEM
scheme, and the constants of the equation are transformed into characteristic parameters. In the
nondimensionalization, firstly the characteristic length L and characteristic velocity U are selected,
and then the nondimensional basic quantities can be obtained according to the ratio of the basic
quantities to the characteristic quantity. It is convenient to nondimensionalize the continuity
equation and momentum conservation equation. The dimensionless quantities of the basic
parameters are defined as follows:

u* =

u
U

(13)

v* =

v
U

(14)

x* =

x
L

(15)

y* =

y
L

(16)

p

p* =
f x* =

f y* =

U 2
fx
U2 L

fy
2

U L

* =


U L

(17)

(18)

(19)

(20)

The basic parameters in Equations (1) and (2) can be replaced by the dimensionless quantities,
and then the equation for dimensionless u-p-ω scheme can be obtained:





u*


 u*






u* v*
+
=0
x* y *
*
p*
u*
1 ω*
* u
+
v
+
+
= f x*
x*
y * x* Re y *
*
p*
v*
1 ω*
* v
+
v
+

= f y*
x*
y * y * Re x*

ω* +

(21)

u* v*

=0
y * x*

where Re = UL/γ is the Reynolds number, and γ stands for the kinematic viscosity of the fluid. In
order to distinguish them, the variables in Equation (21) are marked with asterisks.
According to Equation (21), the coefficient matrices of the dimensionless LSFEM scheme are as
follows:

Energies 2018, 11, 2357

8 of 17


1 0 0
0 

 *

0 
 A =  u0 0 1
 1  0 u* 0 −1 / Re 
0



0

1 0
0 



0 1 0
0 



*

v0 0 0 1 / Re 
 A2 = 
0 v0* 1
0 



1 0 0

0 



0 0 0 0




0 0 0 0
A0 = 

0 0 0 0


 0 0 0 1 




0
 u* 

 *
 *
fx 
v


f = * g = * 


f
p 

 y
 *
ω 
0

 
 

(22)

Due to the little difference of physical parameters in the coefficient matrix, this method can
avoid the large condition number of the stiffness matrix. The derivation process of equation stiffness
matrix and the right-hand function by the dimensionless method are exactly the same as those of the
conventional method. Limited by space, the derivation process will not be addressed in this paper.
2.4. Preconditioning and Iterative Solution Method
The stiffness matrix generated by the conventional LSFEM scheme is a sparse symmetric and a
positive definite, but its condition number may be large due to the large difference of the physical
parameters. While the general preconditioned conjugate gradient methods (PCGMs) can be used to
solve the equations, they are sometimes unable to reduce the matrix condition number. In light of
this, a method, which is a combination of JPCGM and TSEM, is put forward in this paper. Aiming at
effectively reducing the condition number of the stiffness matrix of the pending equations, the basic
idea of this method is stated as follows:
By constructing a matrix Q which approximates the global stiffness matrix and is symmetric,
Equation (11) can be replaced by:

Q-1 K  G = Q-1 F

(23)

There exists a nonsingular matrix W which makes Q = WTW, so W is the Cholesky factorization
of Q. In order to make the coefficient matrix symmetric, the new matrix equation is constructed:

K1  G1 = F1

(24)

where K1 = WQ−1KW−1, G1 = WG, and F = WQ−1F.
In the JPCGM, if the diagonal matrix Q is constructed from the principal diagonal of K, then
the CGM is applied to the preconditioned matrix equation. As a result of the Jacobi preconditioned
conjugate gradient method (JPCGM), the principal diagonal elements of the stiffness matrix are
equal to one, so the differences of 1-norm between rows of K1 are narrowed. However, for some
reasons, the reduction of the condition number is not ideal. Then the two-side equilibration method
(TSEM) is applied to tackle these situations. The key of the TSEM is to obtain the matrix Q so that
the row of matrix K1 has the same 1-norm. Suppose that Q is a diagonal matrix and its main
diagonal elements are Q1, Q2, …, Qi, respectively; i is the dimension of stiffness matrix, and the
diagonal element is defined by:

Energies 2018, 11, 2357

9 of 17

S
Q =
k
i
 K
j =1 kj

(25)

where Kkj is the element of kth row and jth column of matrix K, k = 1, 2, …, i; S is an arbitrary
constant.
Theoretically, no matter what numbers of S there are, there will be no effect on the condition
number of the matrix. However, for a seriously ill-conditioned matrix, the difference of S would
result in different accuracy. If an appropriate value is assigned to S, the condition number of the
matrix K1 will be minimized.
3. Verification by Fluid-Thermal Coupling Problem
3.1. Transformer Winding Model
In order to verify the applicability and efficiency of the proposed algorithm for complex
structures and multi-field coupling problems, a fluid-thermal field coupling problem of an
oil-immersed transformer winding model is taken as instance and analyzed in this paper. A
two-dimensional model of the transformer winding is selected and analyzed [42,43]. The sizes of this
model are listed in Table 1. The fluid area of the model consists of two vertical oil ducts and nine
horizontal oil ducts. The geometric graph is shown in Figure 2a. When meshing the model, the grid
of the oil ducts should be more elaborate than that of the discs, as shown in Figure 2b.
Table 1. Model Sizes.
Component
Total Size of Model
Size of Disc
Length of Insulation Cylinder
Length of Washer
Width of Inlet
Width of Outlet

Disc
winding

Size
0.1 m × 0.125 m
0.088 m × 0.01 m
0.125 m
0.094 m
0.06 m
0.06 m

Washer
Outlet



Insulation
cylinder








Inlet

(a)

(b)

Figure 2. (a) Geometric graph of local winding model; (b) local winding model after meshing.

Energies 2018, 11, 2357

10 of 17

In the coupling field analysis, the physical parameters of the transformer oil are the linear or
quadratic functions of the temperature [10], while others are deemed as constants, as listed in Table
2.
At the inlet, the boundary conditions u = 0, v = 0.05 m/s, and T = 330 K are applied. At the outlet,
the pressure boundary conditions u = 0, p = 0, and T n = 0 are applied.
The no slip boundary, that is, u = 0, v = 0, and T n = 0 , is applied on the washer and
insulating cylinder. Their heat conductivities are very small and thus they are considered as
adiabatic boundaries. The boundary of the disc is a fluid-solid coupling one.
Table 2. Physical parameters of model.
Materials

Transformer oil

Winding

Physical Parameters
Density/kg·m−3
Specific heat capacity/J·(kg·K)−1
Heat conductivity/W·(m·K)−1
Viscosity/Pa·s
Density/kg·m−3
Specific heat capacity/J·(kg·K)−1
Heat conductivity/W·(m·K)−1

Function Fitting
1098.72 − 0.712 T
807.163 + 3.58 T
0.1509 − 7.101 × 10−5 T
0.0846 − 4 × 10−4T + 5 × 10−7 T2
8900
381
387.6

As is known to all, the ohmic loss and eddy-current loss produced in the discs is the heat source
for the whole model, while the ohmic loss accounts for the main part. The effect of the temperature
on its resistance should be taken into account, and the winding loss should be adjusted considering
the influence of the temperature when calculating the temperature field, which is defined in
Reference [47]:

(

P = P0 1 +  (T − T0 )

)

(26)

where P is the windings loss density per element area, P0 is the winding loss density calculated at the
initial temperature T0. When the temperature is 273 K, the density of winding loss per element area
is 2.27 × 105 W/m2. β represents the temperature coefficient of the metal conductors and the value of
the copper is 0.00393 (1/K).
3.2. Velocity Distribution Analysis
The results by the conventional LSFEM [42,43] and the adopted dimensionless LSFEM are
basically equal, the velocity distributions of the local winding model, calculated by the
dimensionless LSFEM and Fluent software, are shown in Figure 3.

(a)

(b)

Figure 3. Velocity distribution contour: (a) calculation result by Fluent; and (b) Calculation result by
dimensionless LSFEM.

Energies 2018, 11, 2357

11 of 17

From Figure 3, we can see that the velocities at the horizontal and vertical oil ducts calculated
by the proposed algorithm and Fluent software are almost the same, which is in accordance with the
results computed by the conventional LSFEM and Fluent software [42]. In order to further illustrate
the accuracy of the proposed algorithm, the velocity components of the two vertical oil ducts in
different directions, x direction and y direction, are extracted, as is drawn in Figure 4.
0.08

0.020

Fluent

inlet-side,Fluent

0.07

LSFEM

outlet-side,Fluent
outlet-side,LSFEM

0.06

0.015

0.05

v/(m/s)

u/(m/s)

inlet-side,LSFEM

0.010

0.04
0.03
0.02

0.005

0.01

0.000
0.00

0.02

0.04

0.06

0.08

y/m

(a)

0.10

0.12

0.00
0.00

0.02

0.04

0.06

0.08

0.10

0.12

0.14

y/m

(b)

Figure 4. (a) Velocity distribution of u along the vertical center line; (b) Velocity distribution of v
along the vertical center line of the vertical oil ducts.

In Figure 4a, from the bottom horizontal oil ducts to the top ones, the velocity of the horizontal
oil decreases first and then increases. The velocity component of the x axis of the top horizontal oil
duct is the largest, while the minimum velocity component of the x axis is in the middle oil duct. The
velocity distributions are also in accord with results in Reference [42]. In Figure 4b, from the inlet to
the top of the oil duct, the velocity of the vertical oil duct on the inlet side decreases in the form of
fluctuations. The maximum velocity is at the place 0.015 m to the inlet. From the bottom of the oil
duct to the outlet, the velocity of the vertical oil duct on the outlet side decreases in the form of
fluctuations. The maximum velocity is at the outlet.
To sum up, the results of the dimensionless LSFEM are basically the same as those of Fluent
software. In such a way, the accuracy of the dimensionless LSFEM scheme for the calculation of fluid
field is proved.
3.3. Temperature Distribution Analysis
The temperature distribution calculated by the proposed coupling algorithm and Fluent
software are shown in Figure 5.

(a)

(b)

Figure 5. Temperature distribution contour: (a) calculation result by Fluent; (b) calculation result by
the upwind finite element method.

Energies 2018, 11, 2357

12 of 17

The temperature distributions are almost identical to the results in Reference [42], which are
obtained by a combination of the conventional LSFEM and UFEM. For the sake of concise
illustration, the discs are numbered in sequence, as shown in Figure 1a. In Figure 5, the temperatures
of the discs increase first and then decrease in the order of one to eight. The temperature of the 8th
disc is the lowest, while the temperatures of the fourth and fifth discs are the highest. The
temperatures on the right-side of discs are higher than that on the left-side. The results obtained by
the proposed algorithm are basically the same as those by the Fluent software.
The temperature values of the 1/4 vertical line on the left and right sides of the discs are
extracted separately, as listed in Table 3.
Table 3. Average temperature of discs calculated by Fluent and the UFEM (K).
Sequence
Number of
Disc
1
2
3
4
5
6
7
8

Left 1/4

Right 1/4

UFEM

Fluent

Error

UFEM

Fluent

Error

341.5
342.8
343.7
344.2
344.3
343.5
342.3
340.9

340.9
342.1
343.1
343.7
343.7
343.0
341.7
340.3

+0.6
+0.7
+0.6
+0.5
+0.6
+0.5
+0.6
+0.6

342.0
343.3
344.2
344.7
344.7
343.9
342.7
341.2

341.5
342.6
343.6
344.2
344.2
343.4
342.1
340.6

+0.5
+0.7
+0.6
+0.5
+0.5
+0.5
+0.6
+0.6

As can be seen from Table 3, the highest temperature can be found on the right-side of the
fourth disc and is 344.7 K, and the lowest temperature is on the left-side of the eight disc and is 340.9
K. The temperature difference is 3.8 K. The temperature of the right-side of the disc is 0.46 K higher
than that of the left-side, on average.
Compared with the results obtained by Fluent software, the thermal field calculated by the
proposed algorithm is slightly higher. The average temperature difference at the left 1/4 and the
right 1/4 are 0.59 K and 0.56 K, respectively. The maximum difference is 0.7 K at the right 1/4 of the
second disc, and its relative error is 0.2%.
The reasons for the difference of the results between the proposed method and Fluent software
are concluded as follows:
(1) Since the indirect coupling method proposed in this paper is a combination of the
dimensionless LSFEM and UFEM, while Fluent software is based on FVM, the different
principle of FEM and FVM could result in some deviations.
(2) Different methods are adopted to deal with boundary conditions by FEM and FVM, which
could bring some influence on the calculation results.
(3) There are eight nodes per element for solving the fluid field by the LSFEM, while nine nodes
per element to solve the thermal field by the UFEM, which adopts the second-order element. In
contrast, Fluent software adopts the linear element. So their interpolation methods are different.
3.4. Convergence Analysis
While the above velocity and temperature distributions of the winding model, obtained by the
Fluent software and the combination of conventional LSFEM and UFEM, respectively, are almost the
same as those obtained by the proposed method in this paper, their convergence rates are different.
The proposed method adopts the nondimensionalization of the Stokes equations and the
preconditioning for the equation’s global stiffness matrix is conducted by the JPCGM and TSEM, so
the corresponding equation converges faster. In order to illustrate the influence of the penalty
function and different LSFEM schemes on the convergence rate, the iteration numbers, convergence
time, and the condition numbers before and after preconditioning of the global stiffness matrix are

Energies 2018, 11, 2357

13 of 17

listed in Table 4, where condition number one stands for the condition number before
preconditioning and condition number two represents the condition number after preconditioning.
As can be seen from Table 4, the larger the value of a penalty function, the larger the condition
number of the equations. However, all the three condition numbers of the conventional scheme can
be reduced to 1.13 × 108, and all the three condition numbers of the dimensionless scheme can be
reduced to 2.55 × 107 by JPCGM and TSEM. Therefore, even if the penalty function is different, the
number of iterations and time for solving the equations is approximately the same after
preconditioning by the JPCGM and TSEM.
For the two different LSFEM schemes, the condition number of the dimensionless scheme is
smaller than that of the conventional scheme, and the number of iterations and the computation time
of the dimensionless scheme is much smaller. It can be explained that the nondimensionalization
process on the equations amounts to a preconditioning and the combination of
nondimensionalization and JPCGM and TSEM can solve the fluid field more efficiently.
Table 4. Convergence of discrete equations with different schemes and penalty functions.
Preconditioned Methods
Penalty Function Size
Condition
Number 1
Condition
Number 2
Conventional
Scheme
Iteration
Numbers
Computation
Time (s)
Condition
Number 1
Condition
Number 2
Dimensionless
Scheme
Iteration
Numbers
Computation
Time (s)

10

4

1.40 × 1018

JPCGM
106

10

1.40 × 1020

1.40 × 1022

8

10

8

JPCGM & TSEM
108

1.88 × 1018

9.89 × 109

1.88 × 1020

108

1.88 × 1022

1.13 × 108
127

127

127

618

614

621

8.27 × 1012

8.23 × 1014

8.23 × 1016

Misconvergence

8.27 × 1012

8.23 × 1014

8.23 × 1016

2.55 × 107

2.55 × 107
24

24

24

125

126

126

Convergence, wrong results

From Table 4 we can see that with the application of the JPCGM only, the conventional LSFEM
scheme cannot get the convergent solution. Thus, the use of the dimensionless LSFEM, whose
iteration number and computation time is meaningless, will obtain a wrong solution. The reason
may be that the equations are seriously ill-conditioned in the neighborhood of zero. On the other
hand, solutions with a good accuracy can be obtained for the two different LSFEMs by the
combination of JPCGM and TSEM.
In addition, we can find that the two different LSFEMs based on the combination of JPCGM and
TSEM converge effectively when the residual velocity is less than the convergence criterion, 1 × 10−6.
However, for the Fluent software, it cannot continually converge when the velocity residuals reach
the residual velocity. On the contrary, the convergence of the two different LSFEMs maintains the
same speed and stays steady. In order to further analyze the minimum residual and convergence
efficiency of the LSFEMs, the convergence criterion is defined as the velocity residuals less than 1 ×
10−15, and the residual data are recorded. Figure 6 gives the convergence curves of the mentioned
methods and shows that the two LSFEMs can get smaller convergence residuals than the Fluent
software.

Energies 2018, 11, 2357

14 of 17

10-1
x-velocity of FVM

10-2

y-velocity of FVM

10-3

x-velocity of dimensionless LSFEM

Residuals

10-4

y-velocity of dimensionless LSFEM

-5

x-velocity of conventional LSFEM

-6

y-velocity of conventional LSFEM

10
10

10-7
10-8
10-9
10-10
10-11
10-12
10-13

0

40

80

120

160

200

240

280

320

360

Iterations
Figure 6. Comparison of convergence curves.

From Figure 6, we can see that the convergence trends of the velocity residuals in x and y
directions are basically the same.
For the Fluent software based on FVM, the velocity residuals converge faster than that of the
conventional LSFEM in the initial iteration stage; but the iteration rate decreases gradually. When
the iteration reaches about 150 steps, the convergence is terminated. The minimum residual of
convergence is larger than 1 × 10−7, and then the residuals oscillate between 1 × 10 −6 and 1 × 10−7.
The convergence rate of the conventional LSFEM is approximately equal to that of Fluent, but
the iterative residual is smaller. When the iteration reaches about 300 steps, the residuals tend to be
stable and oscillate between 1 × 10−11 and 1 × 10−12.
The dimensionless LSFEM scheme converges continuously at a high rate. When the iteration
reaches about 40 steps, the convergence is terminated and then the residuals tend to be stable and
oscillate between 1 × 10−12 and 1 × 10−13. Some conclusions can be achieved as follows:
(1) Among these three calculation methods, the convergence rate of the dimensionless LSFEM
scheme is the fastest, followed by the Fluent software based on the FVM, and finally the
conventional LSFEM. In fact, the convergence rates of the latter two methods are very close.
(2) During the convergence process, the residuals of dimensionless and conventional LSFEM
schemes are much smaller than those of the Fluent software. The smallest residuals can be
obtained by the dimensionless LSFEM scheme while the residuals of the Fluent software are the
largest.
To sum up, the LSFEM has a better convergence and lower residual than the Fluent software.
4. Conclusions
In this paper, an efficient indirect coupling algorithm is adopted to analyze fluid-thermal
coupling problems. Two different LSFEM schemes are analyzed and compared with Fluent
software. Conclusions are drawn as follows:
(1) Taking the results obtained by Fluent as a reference, the relative error of outlet velocity of the
local winding computed by LSFEM is about 0.4%. The temperature difference between the
upwind FEM and Fluent is less than 0.7 K. The LSFEM is stable and the numerical oscillations
can be avoided without adding additional upwind schemes.
(2) The combination of JPCGM and TSEM can effectively reduce the condition number of the
equations and handle the ill-conditioned problems of the stiffness matrix. The larger the penalty

Energies 2018, 11, 2357

15 of 17

functions, the larger the condition number of equations. It should be pointed out that the
condition number can be reduced to the same value by preconditioning.
(3) Compared with the FVM, the algorithm obtained by the dimensionless LSFEM scheme has
better robustness, faster convergence, and lower residuals.
Author Contributions: All authors contributed equally in all the section of this work.
Funding: This research was funded by National Key Research and Development Program of China [Grant No.
2017YFB0902703], National Natural Science Foundation of China [Grant No. 51407075], and Natural Science
Foundation of Hebei Province [Grant No. E2015502004]
Conflicts of Interest: The authors declare no conflict of interest.
References
1.
2.

3.
4.

5.
6.
7.

8.
9.

10.
11.
12.

13.
14.

15.
16.

17.
18.

Heathcote, M.J. The J & P Transformer Book; Johnson & Phillips Ltd.: Karachi, Pakistan, 2007; pp. 121–187.
Higaki, M.; Kako, Y.; Moriyama, M.; Hirano, M.; Hiraishi, K.; Kurita, K. Static electrification and partial
discharges caused by oil flow in forced oil cooled core type transformers. IEEE Trans. Power Appar. Syst.
1979, 98, 1259–1267.
Wang, X.C.; Tao, J.P. Temperature field research of large forced-directed oil cooling transformer.
Transformer 2008, 7, 6–10.
Sen, P.K.; Pansuwan, S. Overloading and loss-of-life assessment guidelines of oil-cooled transformers. In
Proceedings of the 2001 Rural Electric Power Conference, Little Rock, AR, USA, 29 April–1 May 2001; pp.
B4/1–B4/8.
Sefidgaran, M.; Mirzaie, M.; Ebrahimzadeh, A. Reliability model of the power transformer with ONAF
cooling. Int. J. Electr. Power Energy Syst. 2011, 35, 97–104.
Krause, C. Power Transformer insulation-history, technology and design. IEEE Trans. Dielectr. Electr. Insul.
2012, 19, 1941–1947.
Raeisian, L.; Niazmand, H.; Ebrahimnia-Bajestan, E.; Werle, P. Thermal management of a distribution
transformer: an optimization study of the cooling system using CFD and response surface methodology.
Int. J. Electr. Power Energy Syst. 2018, 104, 443–455.
IEEE. IEEE Guide for Loading Mineral-Oil-Immersed Transformers; IEEE: New York, NY, USA, 1996.
Perez, J. Fundamental principles of transformer thermal loading and protection. In Proceedings of the
11th IET International Conference on Developments in Power Systems Protection, Birmingham, UK, 29
March–1 April 2012; pp. 1–6.
Torriano, F.; Chaaban, M.; Picher, P. Numerical study of parameters affecting the temperature
distribution in a disc-type transformer winding. Appl. Therm. Eng. 2010, 30, 2034–2044.
Gong, R.H.; Ruan, J.J.; Chen, J.Z.; Quan, Y.; Wang, J. Analysis and experiment of hot-spot temperature
rise of 110 kV three-phase three-limb transformer. Energies 2017, 10, 1079.
Kranenborg, E.J.; Olsson, C.O.; Samuelsson, B.R.; Lundin, L.Å.; Missing, R.M. Numerical study on mixed
convection and thermal streaking in power transformer windings. In Proceedings of the 5th European
Thermal-Sciences Conference, Eindhoven, The Netherlands, 18–22 May 2008.
Skillen, A.; Revell, A.; Iacovides, H.; Wu, W. Numerical prediction of local hot-spot phenomena in
transformer windings. Appl. Therm. Eng. 2012, 36, 96–105.
Bengang, W.; Hua, H.; Junshang, L.; Nannan, W.; Mingqiu, D.; Tianyi, J. Three dimensional simulation
technology research of split type cooling transformer based on finite volume method. Energy Procedia
2017, 141, 405–410.
Chen, W.; Su, X.; Sun, C.; Pan, C.; Tang, J. Temperature distribution calculation based on FVM for
oil-immersed power transformer windings. Electr. Power Autom. Equip. 2011, 31, 23–27.
Guo, R.; Lou, J.; Wang, Z.; Huang, H.; Wei, B.; Zhang, Y. Simulation and analysis of temperature field of
the discrete cooling system transformer based on FLUENT. In Proceedings of the 2017 1st International
Conference on Electrical Materials and Power Equipment, Xi’an, China, 14–17 May 2017; pp. 287–291.
Tsili, M.A.; Amoiralis, E.I.; Kladas, A.G.; Souflaris, A.T. Power transformer thermal analysis by using an
advanced coupled 3D heat transfer and fluid flow FEM model. Int. J. Therm. Sci. 2012, 53, 188–201.
Li, L.; Niu, S.; Ho, S.L.; Fu, W.N.; Li, Y. A novel approach to investigate the hot-spot temperature rise in
power transformers. IEEE Trans. Magn. 2015, 51, 1–4.

Energies 2018, 11, 2357

19.

20.

21.
22.
23.

24.
25.
26.
27.
28.
29.

30.
31.
32.
33.
34.

35.
36.
37.

38.
39.
40.
41.
42.
43.

16 of 17

Amoiralis, E.I.; Tsili, M.A.; Kladas, A.G.; Souflaris, A.T. Geometry optimization of power transformer
cooling system based on coupled 3D FEM thermal-CFD analysis. In Proceedings of the 2010 14th Biennial
IEEE Conference on Electromagnetic Field Computation, Chicago, IL, USA, 9–12 May 2010.
Torriano, F.; Campelo, H.; Quintela, M.; Labbé, P.; Picher, P. Numerical and experimental thermofluid
investigation of different disc-type power transformer winding arrangements. Int. J. Heat Fluid Flow. 2018,
69, 62–72.
Córdoba, P.A.; Silin, N.; Osorio, D.; Dari, E. An experimental study of natural convection in a distribution
transformer slice model. Int. J. Therm. Sci. 2018, 129, 94–105.
Arabul, A.Y.; Arabul, F.K.; Senol, I. Experimental thermal investigation of an ONAN distribution
transformer by fiber optic sensors. Electr. Power Syst. Res. 2018, 155, 320–330.
Zhang, X.; Daghrah, M.; Wang, Z.; Liu, Q.; Jarman, P.; Negro, M. Experimental verification of
dimensional analysis results on flow distribution and pressure drop for disc-type windings in od cooling
modes. IEEE Trans. Power Deliv. 2018, 33, 1647–1656.
Godina, R.; Rodrigues, E.M.G.; Matias, J.C.O.; Catalão, J.P.S. Effect of loads and other key factors on
oil-transformer ageing: Sustainability benefits and challenges. Energies 2015, 8, 12147–12186.
Ramos, J.C.; Beiza, M.; Gastelurrutia, J.; Rivas, A.; Antón, R.; Larraona, G.S. Numerical modelling of the
natural ventilation of underground transformer substations. Appl. Therm. Eng. 2013, 51, 852–863.
Wang, L.; Zhou, L.; Tang, H.; Wang, D.; Cui, Y. Numerical and experimental validation of variation of
power transformers’ thermal time constants with load factor. Appl. Therm. Eng. 2017, 126, 939–948.
Zhang, Y.; Ho, S.L.; Fu, W. Applying response surface method to oil-immersed transformer cooling
system for design optimization. IEEE Trans. Magn. 2018, 1–5.
Liao, C.; Ruan, J.; Liu, C.; Wen, W.; Du, Z. 3-D coupled electromagnetic-fluid-thermal analysis of
oil-immersed triangular wound core transformer. IEEE Trans. Magn. 2014, 50, 1–4.
Wang, Q.; Wang, H.; Peng, Z.; Liu, P.; Zhang, T.; Hu, W. 3-D coupled electromagnetic-fluid-thermal
analysis of epoxy impregnated paper converter transformer bushings. IEEE Trans. Dielectr. Electr. Insul.
2017, 24, 630–638.
Liu, Y.; Li, G.; Guan, L.; Li, Z. The single-active-part structure of the UHVDC converter transformer with
the UHVAC power grid. CSEE J. Power Energy Syst. 2017, 3, 243–252.
Zhang, B.Z.; Yin, J.A.; Zhang, H.J. Numerical method of fluid mechanics. Mech. Eng. Press. 2003, 68–180.
Hendriana, D.; Bathe, K. On upwind methods for parabolic finite elements in incompressible flows. Int. J.
Numer. Methods Eng. 2015, 47, 317–340.
Zienkiewicz, O.C.; Taylor, R.L.; Nithiarasu, P. The Finite Element Method for Fluid Dynamics, 6th ed.;
Elsevier Butterworth-Heinemann: Oxford, UK, 2005; pp. 525–537.
Brooks, A.N.; Hughes, T.J.R. Streamline upwind/petrov-galerkin formulations for convection dominated
flows with particular emphasis on the incompressible navier-stokes equations. Comput. Methods Appl.
Mech. Eng. 2015, 32, 199–259.
Heinrich, J.C.; Huyakorn, P.S.; Zienkiewicz, O.C.; Mitchell, A.R. An ‘upwind’ finite element scheme for
two‐dimensional convective transport equation. Int. J. Numer. Methods Eng. 2010, 11, 131–143.
Liu, G.; Jin, Y.J.; Ma, Y.Q.; Wang, L.P.; Chi, C.; Li, L. Two-dimensional temperature field analysis of
oil-immersed transformer based on non-uniformly heat source. High Volt. Eng. 2017, 43, 3361–3370.
Wang, Y.Q.; Ma, L.; Lü, F.C.; Bi, J.G.; Wang, L.; Wan, T. Calculation of 3D temperature field of oil
immersed transformer by the combination of the finite element and finite volume method. High Volt. Eng.
2014, 40, 3179–3185.
Jiang, B.N. The least-squares finite element method. Int. J. Numer. Methods Eng. 1998, 54, 3591–3610.
Bochev, P.B.; Gunzburger, M.D. Least-Squares Finite Element Methods; Springer: Berlin, Germany, 2009; pp.
S23–S24.
Pontaza, J.P. A least-squares finite element formulation for unsteady incompressible flows with improved
velocity–pressure coupling. J. Comput. Phys. 2006, 217, 563–588.
Tao, S.; Yang, Z.; Jiang, B.; Gu, W.J. Application comparison of least square finite element method and
finite volume method in CFD. Comput. Aided Eng. 2012, 21, 1–6.
Xie, Y.Q.; Li, L.; Song, Y.W.; Wang, S.B. Multi-physical field coupled method for temperature rise of
winding in oil-immersed power transformer. Proc. CSEE 2016, 36, 5957–5965.
Xie, Y.Q. Study on flow field and temperature field coupling finite element methods in oil-immersed
power transformer. Ph.D. Thesis, North China Electric Power University (Beijing), Beijing, China, July
2017.

Energies 2018, 11, 2357

44.
45.
46.
47.

17 of 17

Fialko, S.Y.; Zeglen, F. Preconditioned conjugate gradient method for solution of large finite element
problems on CPU and GPU. J. Telecommun. Inform. Technol. 2016, 2, 26–33.
Wallot, J. XLIX. Dimensional analysis. Lond. Edinb. Dublin Philos. Mag. J. Sci. 2009, 3, 496,
doi:10.1080/14786440208564219.
Liu, C.S. A two-side equilibration method to reduce the condition number of an ill-posed linear system.
Comput. Model. Eng. Sci. 2013, 91, 17–42.
Liao, C.B.; Ruan, J.J.; Liu, C.; Wen, W.; Wang, S.S.; Liang, S.Y. Comprehensive analysis of 3-D
electromagnetic-fluid-thermal fields of oil-immersed transformer. Electr. Power Autom. Equip. 2015, 35,
150–155.
© 2018 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access
article distributed under the terms and conditions of the Creative Commons Attribution
(CC BY) license (http://creativecommons.org/licenses/by/4.0/).